I’m in an apt. and the power has been shutting off lately. It doesn’t trip any of the breakers in the breaker box inside the apt. but it does trip the master breaker on the box outside. Thought it was an oven issue but it still happens with the oven breaker off.

Visual inspection of the breaker box outside shows one of the wires looks a bit corroded. Wires to/from the rest of the units are a nice copper color. Is that a red flag?

Landlord is dragging their feet and telling us to talk to the electric company, and electric company is saying to call a licensed electrician, so I’m just trying to understand the issue so hopefully the landlord will listen to me.

        • bobs_monkey@lemmy.zip
          link
          fedilink
          arrow-up
          4
          ·
          edit-2
          2 days ago

          Cause by heat scoring, and beneath the traces of green oxidation is heat blackenng. That leg specifically has been over heated over time, causing the discoloration reaction. If it was natural oxidation (like the statue of liberty, for example), then all the wires would be the same color.

          Copper wire for a long time has been manufactured in such a way that it is resistant to ambient oxidation. When excessive heat is induced in the wire, that natural protection is broken down and then it is subject to turning green, but generally only where heat has damaged the wire.

          Here is a basic idea of how cables are made to not oxidize when they’re just sitt ng there in normal operation.